The full ratings overview. Need an MTO configuration outside this envelope? Talk to an engineer.
| Normal Voltage Rating | 415Y/240 VAC · 480Y/277 VAC (opt) · 208Y/120 VAC (opt) |
|---|---|
| Input Connection / Phasing | 3Ø-Y, 4-wire |
| Frequency | 60 Hz |
| Main Input Circuit Breaker | Up to 600A · 100% rated, LSI (80% rated, LSI optional) |
| SCCR (Interrupt Rating) | 14 kA @ 480VAC / 65 kA @ 240VAC · 65 kA @ 480VAC (optional) |
| Distribution Panel | (84) single-pole branch-circuit positions |
| Distribution Branch Breakers | (28) 30A/3-pole · (28) 50A/3-pole (optional) · 20A–150A range |
| Metering / Monitoring | InSight BCMS with local touchscreen display · ±0.5% true-RMS |
| Surge Protection | Optional — up to 100 kA |
| Isolated Neutral | 200% |
| Enclosure | Indoor UL Type 1 · front, back & side access · top & bottom cable entry · seismic tested |
| Finish | Slate blue-grey standard · custom colors available |
| Dimensions (W × D × H) | 24 in × 12 in × 90 in (610 × 305 × 2032 mm) |
| Weight (max) | 370 ±20 lbs (168 ±9 kg) |
| Configurations | Free-standing · wall-mounted · back-to-back |
| Listings | UL listed · Siemens Approved OEM · USA manufactured · BABA-compliant |
| Lead Time | 4 weeks, guaranteed anywhere in the USA |