⚡ We Offer Rapid Deployment Packages ☎ (866) 645-1281 ✉ sales@criticalpowerpanels.com
Technical

CP Series RPP specifications

The full ratings overview. Need an MTO configuration outside this envelope? Talk to an engineer.

Normal Voltage Rating415Y/240 VAC · 480Y/277 VAC (opt) · 208Y/120 VAC (opt)
Input Connection / Phasing3Ø-Y, 4-wire
Frequency60 Hz
Main Input Circuit BreakerUp to 600A · 100% rated, LSI (80% rated, LSI optional)
SCCR (Interrupt Rating)14 kA @ 480VAC / 65 kA @ 240VAC · 65 kA @ 480VAC (optional)
Distribution Panel(84) single-pole branch-circuit positions
Distribution Branch Breakers(28) 30A/3-pole · (28) 50A/3-pole (optional) · 20A–150A range
Metering / MonitoringInSight BCMS with local touchscreen display · ±0.5% true-RMS
Surge ProtectionOptional — up to 100 kA
Isolated Neutral200%
EnclosureIndoor UL Type 1 · front, back & side access · top & bottom cable entry · seismic tested
FinishSlate blue-grey standard · custom colors available
Dimensions (W × D × H)24 in × 12 in × 90 in (610 × 305 × 2032 mm)
Weight (max)370 ±20 lbs (168 ±9 kg)
ConfigurationsFree-standing · wall-mounted · back-to-back
ListingsUL listed · Siemens Approved OEM · USA manufactured · BABA-compliant
Lead Time4 weeks, guaranteed anywhere in the USA
Request a Spec Sheet